H26: Number of Auto Restart Attempt
Range:
0-10 (Default: 0)
Description:
This parameter sets the number of restart tries after a fault occurs. The auto
restart will not reset faults such as OHT, LVT, EXT, HWT, etc. This
function is active when [DRV] is set to 1 or 2 {Run/Stop via control
terminal}.
H27: Auto Restart Time
Range:
0-60sec. (Default: 1.0sec.)
Description:
This parameter sets the time between restart tries.
The drive has the ability to automatically reset itself after a fault occurs.
The drive will reset itself up to the amount of times set in H26. The drive
will wait the amount of time set in AFN 26 after a fault before attempting a
restart. The motor may be coasting when the restart occurs. To catch the
spinning load use the speed search function. Set H22 to ‘xx1x’. See H22 ~
H25.
This function is disabled when a low voltage (LV) trip, drive disable (BX)
or Arm short occurs.
z
Note:
The drive decreases the retry number by one after each fault
occurs. When restarted without a fault the drive increases the retry number
by one after 30 seconds.
91
6 - Parameter Descriptions
Output Frequency
Restart with
Speed Search
t: H27
Restart with
Speed Search
1st Fault
2nd Fault
Time
Summary of Contents for RSi GX Series
Page 7: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 9...
Page 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Page 25: ...3 Receiving and Installation 19...
Page 41: ...4 Operation 35...
Page 53: ...5 Parameter List 47...
Page 62: ...Notes 56 5 Parameter List...
Page 63: ...6 Parameter Descriptions 57...
Page 135: ...7 Remote Communication 129...
Page 149: ...8 Troubleshooting Maintenance 143...
Page 162: ...Notes 156 8 Troubleshooting Maintenance...
Page 163: ...9 Options 157...
Page 165: ...10 Appendices 159...