F20: Jog Frequency
Range:
0 - 400 Hz (Default: 10.00Hz)
Description:
This parameter sets the frequency for Jog operation. It cannot be set above
F21 (Max. frequency). Jog operation overrides all other applications except
Dwell operation. Therefore, if Jog frequency command is entered in the
middle of Multi-step, Up-Down or 3-wire operation, operation is executed
at Jog frequency.
•
Set the desired jog frequency in F20.
•
Select a terminal from P1 - P8 to use for this setting.
•
If P5 is set for Jog operation, set I21 to 4 (Jog).
•
Jog frequency can be set within the range of F21 (Max. frequency) and
F22 (Start frequency).
•
See I21 (Multi-function input terminal P5 define, page 114)
F21: Maximum Frequency
Range:
40 - 400 Hz (Default: 60.00Hz)
Description:
This parameter sets the highest frequency the drive can output. It is
frequency reference for Accel/Decel (See H70, page 101).
CAUTION
: Any frequency cannot be set above F21 (Max. frequency)
except F22 (Base frequency).
•
If H40 (page 95) is set to 3 (sensorless vector), Max. frequency is settable
up to 300Hz.
71
6 - Parameter Descriptions
P4-CM
ON
Time
Time
FX-CM
ON
Time
RX-CM
ON
Time
Output Frequency
ON
5Hz
5Hz
Jog Frequency
Summary of Contents for RSi GX Series
Page 7: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 9...
Page 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Page 25: ...3 Receiving and Installation 19...
Page 41: ...4 Operation 35...
Page 53: ...5 Parameter List 47...
Page 62: ...Notes 56 5 Parameter List...
Page 63: ...6 Parameter Descriptions 57...
Page 135: ...7 Remote Communication 129...
Page 149: ...8 Troubleshooting Maintenance 143...
Page 162: ...Notes 156 8 Troubleshooting Maintenance...
Page 163: ...9 Options 157...
Page 165: ...10 Appendices 159...