Grounding:
•
The drive contains high power and high frequency switching devices, leakage current
may flow between the drive and ground. Ground the drive to avoid electrical shock.
•
If multiple drives are installed near each other, each must be connected to ground
directly. Take care not to form a ground loop between the drives and the grounding
location.
•
The protective earth conductor must be the first one in being connected and the last one
in being disconnected.
•
The grounding wire shall comply with all local regulations. As a minimum,The
grounding wire should be at least the thickness that is listed in the following table and as
short as possible. Connect the grounding point as near to the drive as possible.
•
Use the Type 3 grounding method (Ground impedance: Below 100
W
) for 230V class
drives.
•
Use the Special Type 3 grounding method (Ground impedance: Below 10
W
) for 460V
class drives.
•
Use the dedicated ground terminal to ground the drive. Do not use the screw in the case
or chassis, etc. for grounding.
Grounding Procedure:
•
Remove the front cover.
•
Connect the grounding wire to the ground terminal through the opening for ground
terminal as shown above. Enter the screw driver from vertical to the terminal and secure
the screw tightly.
27
3 - RECEIVING AND INSTALLATION
Motor Capacity
Grounding wire dimensions, AWG (mm_)
200V class
400V class
1.0-5.0 HP
12 (3.5)
14 (2)
Ground Screw
Summary of Contents for RSi GX Series
Page 7: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 9...
Page 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Page 25: ...3 Receiving and Installation 19...
Page 41: ...4 Operation 35...
Page 53: ...5 Parameter List 47...
Page 62: ...Notes 56 5 Parameter List...
Page 63: ...6 Parameter Descriptions 57...
Page 135: ...7 Remote Communication 129...
Page 149: ...8 Troubleshooting Maintenance 143...
Page 162: ...Notes 156 8 Troubleshooting Maintenance...
Page 163: ...9 Options 157...
Page 165: ...10 Appendices 159...