6.1
Drive Group
0.00: Frequency Command
Range:
0 - 400 Hz. (Default 0.00)
Description:
This parameter sets the frequency that the drive is commanded to output,
when the drive is operating from the keypad. Frequency setting mode must
be set to 1.
Drive Mode:
Parameter Display:
During Stop
Frequency Command
During Run
Output Frequency
Multi-step operation
Multi-step frequency 0.
It cannot be set greater than F21- [Max frequency].
ACC/dEC: Accel/Decel Time
Range:
0-6000 sec. (Default: Accel -5.0 s., Decel -10.0s.)
Description:
The acceleration time sets the amount of time to reach the maximum
frequency upon a start command. The deceleration time sets the amount of
time to stop from the maximum frequency. During Multi-Accel/Decel
operation, this parameter serves as Accel/Decel time 0.
58
6 - Parameter Descriptions
Output Frequency
Time
Acc. Pattern
Dec. Pattern
Max. freq.
Related functions:
FU1-20 [Max freq]
FU2-70 [Ref freq for accel/decel]
FU2-71 [Accel/decel time scale]
I/O-12 to I/O-14 [Multi-function input terminal P1,
P2, P3]
I/O-25 to I/O-38 [Acc/dec time for step frequency]
FU-70: select the frequency to be targeted for
acceleration and deceleration [Max freq, Delta freq]
FU2-71: select the time scale. [0.01, 0.2, 1]
I/O-12 to I/O-14: set the terminal function of
P1,P2,P3 terminal outputs
I/O-25 to I/O-38: preset the accel/decel time
activated via multi-function inputs (P1,P2,P3)
Summary of Contents for RSi GX Series
Page 7: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 9...
Page 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Page 25: ...3 Receiving and Installation 19...
Page 41: ...4 Operation 35...
Page 53: ...5 Parameter List 47...
Page 62: ...Notes 56 5 Parameter List...
Page 63: ...6 Parameter Descriptions 57...
Page 135: ...7 Remote Communication 129...
Page 149: ...8 Troubleshooting Maintenance 143...
Page 162: ...Notes 156 8 Troubleshooting Maintenance...
Page 163: ...9 Options 157...
Page 165: ...10 Appendices 159...