H20: Power ON Start Select
Range:
0-1 (Default: 0)
Description:
This parameter is activated when DRV is set to 1 or 2 (Run/Stop via Control
terminal).
Display:
Function:
0
The drive requires the start command to open and reclose
upon power loss.
1
The drive will restart upon return of power if run
command is still active.
H21: Restart After Fault Reset Selection
Range:
0 - 1 (Default:0)
Description:
This parameter is activated when DRV is set to 1 or 2 (Run/Stop via Control
terminal).
Display:
Function:
0
The drive requires the start command to open and reclose
upon a fault reset.
1
The drive will restart upon a fault reset if run command is
still active.
87
6 - Parameter Descriptions
Particular attention must be directed to this function due
to potential hazard as motor starts to run suddenly upon
applying AC input power.
CAUTION
Particular attention must be directed to this function due to
potential hazard as motor starts to run suddenly upon applying
AC input power.
CAUTION
Run
command
Frequency
Input voltage
When H20 is 0
When H20 is 1
Summary of Contents for RSi GX Series
Page 7: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 9...
Page 24: ...Notes 18 2 TECHNICAL SPECIFICATIONS...
Page 25: ...3 Receiving and Installation 19...
Page 41: ...4 Operation 35...
Page 53: ...5 Parameter List 47...
Page 62: ...Notes 56 5 Parameter List...
Page 63: ...6 Parameter Descriptions 57...
Page 135: ...7 Remote Communication 129...
Page 149: ...8 Troubleshooting Maintenance 143...
Page 162: ...Notes 156 8 Troubleshooting Maintenance...
Page 163: ...9 Options 157...
Page 165: ...10 Appendices 159...