Parameter Initialize
How to initialize parameters of all four groups in H93
42
4 - Operation
1
In H0, press the Enter (
) key once.
2
Code number of H0 is displayed.
Increase the value to 3 by pressing the Up (
p
) key.
3
In 3, press the Left (
t
) key once to move the cursor to the left.
4
03 is displayed. 0 in 03 is active.
Increase the value to 9 by pressing the Up (
p
) key.
5
93 is set.
Press the Enter (
) key once.
6
The parameter number is displayed.
Press the Enter (
) key once.
7
Present setting is 0.
Press the Up (
p
) key once to set to 1 to activate parameter initialize.
8
Press the Enter (
) key once.
9
Return to the parameter number after blinking. Parameter initialize has
been complete. Press the either Left (
t
) or Right (
u
) key.
10
Return to H0.
z
Note:
This parameter is used to reset the drive to its factory defaults.
H 0
1
3
H 93
0
1
H 93
H 0
03
93