Safety instructions
9
isoLR275_D00127_00_M_XXEN/07.2018
1.3
Directions for installation
The terminals
and KE have to be connected by a separate wire to the pro-
tective conductor (PE). If the terminals L1, L2 of the device are connected to
an IT system under operation, the terminals
and KE must not be discon-
nected from the protective conductor (PE).
In order to check the proper connection of the device, it is recommended to
carry out a functional test using an insulation fault, e.g. via a suitable resis-
tance, before starting the ISOMETER®.
Risk of property damage due to unprofessional
installation!
If more than one insulation monitoring device is connected
to aconductively connected system, the system can be da-
maged. If several devices are connected, the device does not
function and does not signal insulation faults. Make sure
that only one insulation monitoring device is connected in
each conductively connected system.
Ensure disconnection from the IT system!
When insulation or voltage tests are to be carried out, the de-
vice must be isolated from the system for the test period. Other-
wise, the device may be damaged.
CAUTION
CAUTION