Commissioning flow chart (in three parts)
24
isoLR275_D00127_00_M_XXEN/07.2018
Commissioning of the ISOMETER® (2)
Connect the supply
voltage US
The ISOMETER carries out a
self test. The display indicates
the insulation value after finishing
the measurement
Shall the basic setting
be changed?
Alarm1 = 4 k
Ω
Alarm2 = 1 k
Ω
K1/K2 = N/O operation
Memory = off
no
yes
Does one of the alarm LEDs
light up?
Select
ISO SETUP
(see chapter operation and setting)
no
yes
The insulation value of the system
being monitored is below the preset
response value. Change the response
value or improve the insulation
condition of the system
Set the clock
Connect the voltage Un of the
IT system to be monitored