Safety instructions
10
isoLR275_D00127_00_M_XXEN/07.2018
The device variant -3… is delivered with the following factory set-
ting:
Please check if the factory setting of the ISOMETER® complies with the requi-
rements of the IT system to be monitored.
Response value
R
an
For correct setting of the response value in kΩ, it is useful to know the present
value of the insulation resistance of the electrical installation.
ISO SETUP:
Alarm 1/Alarm 2
(response values)
= 4 kΩ/1 kΩ
ISO SETUP:
Operating mode K1/K2 = N/O operation
(N.O.)
ISO SETUP:
Memory = off
ISO ADVANCED:
System leakage capacitance
Measurement method
=
=
150
µF
AMP
COM SETUP:
Bus address = 3 (Slave)
When the AC system being monitored contains galvanically
coupled DC circuits:
An insulation fault can only be monitored correctly when the
rectifiers carry a continuous load current of 5…10 mA.