Technical data isoLR275 with AGH-LR
67
isoLR275_D00127_00_M_XXEN/07.2018
7.2
AGH-LR data in tabular form
Insulation coordination acc. to IEC 60664-1
Rated insulation voltage................................................................................................................................... AC 800 V
Rated impulse voltage/pollution degree ............................................................................................................. 8 kV/3
Voltage ranges
Nominal system voltage
U
n
........................................................................... AC, 3(N)AC 0…793 V, DC 0…1,100 V
Nominal frequency
f
n
.......................................................................................................................... DC, 10…460 Hz
Max. AC voltage
U~
in the frequency range
f
n
= 0.1…10 Hz: ...........................................
U
~ max
= 110 V/Hz *
f
n
Environment/EMC
EMC ............................................................................................................................................. IEC 61326-2-4 Ed. 1.0
Operating temperature ...................................................................................................................... -25 ºC…+65 ºC
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ........................................................... 3K5 (with condensation and formation of ice)
Transport (IEC 60721-3-2)................................................................... 2K3 (with condensation and formation of ice)
Long-term storage (IEC 60721-3-1)................................................... 1K4 (with condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ............................................................................................................................. 3M7
Transport (IEC 60721-3-2) ..................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1) ...................................................................................................................... 1M3
Connection
Connection .................................................................................................................................... screw-type terminals
Connection, rigid/flexible.............................................................................................. 0.2…4 mm
2
/0.2…2.5 mm
2
Connection flexible with ferrules, without/with plastic sleeve.......................................................... 0.25…2.5 mm
2
Tightening torque ............................................................................................................................................... 0.5 Nm
Conductor sizes (AWG)...................................................................................................................................... 24…12
Cable length between isoLR275 and AGH-LR .................................................................................................
≤
0.5 m
Other
Operating mode............................................................................................................................ continuous operation
Mounting .................................................................................................... cooling slots must be ventilated vertically!
Distance to adjacent devices .........................................................................................................................
≥
30 mm
Degree of protection, internal components (DIN EN 60529) .................................................................................. IP30
Degree of protection, terminals (DIN EN 60529)..................................................................................................... IP20