Serial interface
60
isoLR275_D00127_00_M_XXEN/07.2018
6.3.2
BMS slave
All isoLR275 devices are factory-set to slave mode (address 3). In a BMS net-
work, one address must be selected from the address range 2...30 for each sla-
ve. There may be no gaps of more than five subsequent addresses, so that all
slaves can be scanned by the master. For isoLR275 a BMS address can be se-
lected from the address range 1...30. When assigning the addresses, also other
devices such as EDS4xx must be considered.
The receipt of the BMS data is indicated by a flashing point on the display on
the right of the measuring pulse indication.
Flashing point:
BMS data re-
ceived
If no flashing point appears, it may be attributed to the following:
No master available in the network
More than one master available in the network
RS-485 interface (terminals A/B) not connected or reversed