11
isoLR275_D00127_00_M_XXEN/07.2018
2. Function
2.1
Device features isoLR275
ISOMETER® for IT AC systems with galvanically connected rectifiers or
converters
and for IT DC systems (IT = unearthed systems)
Particularly suited for monitoring electrical installations with a low level
of resistance
isoLR275 is always operated in conjunction with AGH-LR
Automatic adaptation to the existing system leakage capacitance
-Measurement method (European Patent: EP 0 654 673 B1)
Choice of measurement methods to meet different requirements
Two separately adjustable response ranges of 0.2 kΩ…100 kΩ each
(Alarm 1, Alarm 2)
Two-line LC display
Automatic device self test
Memory with real-time clock to store alarm messages with date and
time stamp
BMS interface (Bender Measuring Device Interface) for communication
with other Bender devices (RS-485 galvanically isolated)
Internal disconnection of the ISOMETER® from the IT system to be
monitored (via control signal; terminals F1/F2), e.g. if several
ISOMETER®s are interconnected
Current output 0(4)…20 mA (electrically isolated) in relation to the
insulation value measured in the system
AMP
Plus