Technical data isoLR275 with AGH-LR
64
isoLR275_D00127_00_M_XXEN/07.2018
For UL applications:
Nominal system voltage
U
n
.......................................................................................................................... via AGH-LR
isoLR275-335:
Supply voltage
U
s
(also see nameplate) ................................................................................................ AC 88…250 V
Frequency range
U
s
................................................................................................................................... 42…460 Hz
Power consumption AC .................................................................................................................................
≤
21,5 VA
Supply voltage
U
s
(also see nameplate) ................................................................................................ DC 80…250 V
Power consumption DC ...................................................................................................................................
≤
5,5 VA
isoLR275-327:
Supply voltage
U
s
(also see nameplate) .................................................................................................. DC 24…65 V
Power consumption ............................................................................................................................................
≤
6 VA
Response values
Response value
R
an1
................................................................................................................................. 0.2…100 kΩ
Factory setting
R
an1
(Alarm1) .................................................................................................................................
4
kΩ
Response value
R
an2
.................................................................................................................................. 0.2…100 kΩ
Factory setting
R
an2
(Alarm2) .................................................................................................................................
1
kΩ
Relative uncertainty (7 kΩ…100 kΩ) (nach IEC 61557-8) .............................................................................. ±15 %
Relative uncertainty (0.2 kΩ…7 kΩ) .................................................................................................................. ±1 kΩ
Response time
t
an
...................................................................................................... see table starting from page 44
Hysteresis ................................................................................................................................................... 25 %, +1 kΩ
Measuring circuit
Measuring voltage
U
m
(peak value)..................................................................................................................... ±50 V
Measuring current
I
m
(at
R
F
= 0 Ω)................................................................................................................
≤
1.5 mA
Internal DC resistance
R
i
.....................................................................................................................................
≥
35 kΩ
Impedance
Z
i
at 50 Hz .......................................................................................................................................
≥
35 kΩ
Permissible extraneous DC voltage
U
fg
....................................................................................................
≤
DC 1,100 V
Max. system leakage capacitance
C
e
..............................................................................................
≤
500 μF (150 μF)*
Displays
Display....................................................................................................................................... backlit two-line display
Characters (number/height) ..................................................................................................................... 2 x 16/4 mm
Display range measured value............................................................................................................... 0.2 kΩ…1 MΩ
Operating uncertainty............................................................................................................................. ±15%, ±1 kΩ