Serial interface
59
isoLR275_D00127_00_M_XXEN/07.2018
6.3.1
BMS master
A master can query all warning and operational messages from a slave.
If the bus address 1 has been selected for one isoLR275, the device automati-
cally represents the master, that means that all addresses between 1 and 150
are cyclically scanned for alarm and operational messages via the BMS bus. If
the master receives no answer from five subsequent addresses, the scanning
cycle is started again. If the master recognises incorrect answers from a slave,
the fault message "Fault RS485" will appear on the display.
Fault causes may be:
Addresses are assigned twice
A second master exists on the BMS bus
Interference signals occur on the bus lines
A defective device is connected to the bus
Terminating resistors are not activated
Fa u l t R S 4 8 5
R s = 0 1 1 k
W
.
H