Operation and configuration
42
isoLR275_D00127_00_M_XXEN/07.2018
5.4.3
Memory setting (on/off)
Memory: on
= Fault memory is activated
The device must be reset with the reset button after
clearing the fault.
Memory: off
= Fault memory deactivated (factory setting)
5.4.4
Current output for external measuring instruments
Factory setting: 0…20 mA
The current output of the isoLR275 can be set to
"0…20 mA" or "4…20 mA" via the "M+/M-:" menu item. The maximum load is
500 Ω.
5.4.5
Adjusting the current output to the centre scale mark of ex-
ternal measuring instruments
Factory setting = 28 kΩ
Use the menu item "8. M+/M- Ri:“ in the ISO SETUP menu to select a centre
scale mark.
8. M+/M- Ri:28kΩ = centre scale
R
Sk
= 28 kΩ (factory setting)
8. M+/M- Ri:120kΩ = centre scale
R
Sk
=120kΩ (compatible to IRDH275…-4…)
During the automatic self test, the alarm relays are not switched
over.
In case of a malfunction of the ISOMETER®, the relay K2 will auto-
matically be activated as a device error relay.