Serial interface
62
isoLR275_D00127_00_M_XXEN/07.2018
BMS bus address ranges (internal bus)
Addresses*
Device
Note
0
There is no device with address 0 ! Informa-
tion sent to address 0 applies to all devices
connected to the interfaces (broadcast)
1…30 IRDH275B/
375B/575;
isoPV
isoLR275
Insulation monitoring devices
1…30 FTC4…
Protocol converters
1…90 COM460IP
Protocol converters
1…90 EDS46…/49… Insulation fault locators (EDS)
1…150 MK800
Alarm indicator and test combination
111…119 PGH47…
Locating current injector
121…150 PGH47…E
Locating current injector
* Assign the addresses consecutively, there must be no gaps
greater than five in the respective ranges
(1…30, 31…60, 61…90, 111…119 and 121…151).