Function
16
isoLR275_D00127_00_M_XXEN/07.2018
2.4.3
Current output for external measuring instrument
The current output of isoLR275 is electrically isolated from the device electro-
nics and the RS-485 interface.
An output current range of 0…20 mA or 4…20 mA can be selected by means
of the ISO SETUP menu, refer to page 36. In addition, the centre scale mark can
be set to 28 kΩ or 120 kΩ, related to an external measuring instrument.
Alarm
message
Description
Actions
Connection
PE?
No low-resistance
connection bet-
ween the terminals
and KE to
earth (PE).
1. Check the wiring of the terminals
and KE to earth (PE)
2. Press the "TEST" button
3. Switch the supply voltage on and off
Device error
x
Internal device
error
1. Press the "TEST" button
2. Switch the supply voltage off and on
3. Please contact Bender
If, for functional reasons, the supply voltage cannot be
switched on or off, a reset of the sequence control system can
be carried out by pressing the buttons "ESC", "RESET" and
"MENU“ simultaneously.