5 Configuration and startup
5.4 Configuration of the LioN-P
EtherNet/IP modules
The Exclusive Owner connection type is only available for modules with an
output function (variants 16DIO, 16DO and 8DI/8DO).
By selecting the corresponding instance ID of the assembly object, you decide
how many items of IO process data the LioN-P module makes available to
the user and whether diagnostic data is to be added.
LioN-P 16DIO modules can be used everywhere and offer you different
profiles as the basic system configuration. With these you can preconfigure
a 16DIO module as a 16DI, 16DO or 8DI/8DO module and replace it, for
example.
With LioN-P 16DIO modules with DCU function, the process data is expanded
to include an additional 18 bytes in both data directions. Further details on
the data structure are described in section
Bit assignment of the process data
on page 61.
The LioN-P modules provide the following connections and assembly IDs:
Manual LioN-P EtherNet/IP
Version 2.0 11/2017