8.1 Start page/status page (Status)
8 Integrated web server
8 Integrated web server
The LioN-P modules are equipped with an integrated web server which
makes functions available for the configuration of modules and display of
status and diagnostic information.
Using a standard web browser, the provided functions can be accessed via
an existing TCP/IP connection.
Attention:
To use the web server, the modules need their own IP
address. In accordance with the EtherNet/IP standard, all EtherNet/IP
devices are shipped with the IP address 192.168.1.1. Consequently,
the modules must be assigned a free IP address that differs from the
factory setting prior to use of the web server. The assignment of the
IP address is described in this manual in section
on page 27.
8.1 Start page/status page (Status)
In the address line of your web browser enter http://, followed by the IP
address, e.g. http://192.168.1.1. If the module start page doe snot open,
check your browser and firewall settings.
This website shows the current status of the overall module and the respective
status of the individual channels. Pending diagnoses are notified as for the
controller.
The process data
Consuming/Producing Data
, including the diagnostic
Diagnostic
, is shown as hexadecimal in the
PLC process data
as well as
graphically in the
Module overview
and
Channel overview
areas. The coding
of the diagnostic can be found in section
Bit assignment of the process data
on page 61.
The table
Channel overview
is broken down into three different areas. The
status of the physical input and output data for the channels as well as the
process data sent to and received from the controller is displayed. Channel
errors are registered in the last column.
Manual LioN-P EtherNet/IP
Version 2.0 11/2017