5 Configuration and startup
5.4 Configuration of the LioN-P
EtherNet/IP modules
defines the monitoring procedure for the individual digital output currents for
each channel.
The delay time starts after a change to the output channel status. If an output
is activated (rising edge) or deactivated (falling edge) the output monitoring
does not start until the delay time expires. Any fault conditions that arise after
this delay are reported as diagnostics.
The adjustable value range for the delay time is 0 to 255 ms. The default value
is 80 ms. When the output channel is in the static state, (channel permanently
switched on or off) the value is 100 ms.
MSB
LSB
Bit
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
Word 0
Surveillance timeout port X1, channel A (pin 4), value range 0...255, default value 80
Word 1
Surveillance timeout port X1, channel B (pin 2), value range 0...255, default value 80
:
:
Word 14 Surveillance timeout port X8, channel A (pin 4), value range 0...255, default value 80
Word 15 Surveillance timeout port X8, channel B (pin 2), value range 0...255, default value 80
Table 25: Surveillance timeout values for the 16DO module or 16DIO
module with DIO, DO and 8DI/8DO profiles
MSB
LSB
Bit
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
Word 0
Surveillance timeout port X5, channel A (pin 4), value range 0...255, default value 80
Word 1
Surveillance timeout port X5, channel B (pin 2), value range 0...255, default value 80
:
:
Word 6
Surveillance timeout port X8, channel A (pin 4), value range 0...255, default value 80
Word 7
Surveillance timeout port X8, channel B (pin 2), value range 0...255, default value 80
Table 26: Surveillance timeout values for the 8DI/8DO module
Manual LioN-P EtherNet/IP
Version 2.0 11/2017
41