Commissioning
EL70x1
206
Version: 4.4
Index A010 STM Diag data Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
A010:0
STM Diag data Ch.1
Maximum subindex
UINT8
RO
0x11 (17
dec
)
A010:01
Saturated
Driver stage operates with maximum duty cycle
BOOLEAN
RO
0x00 (0
dec
)
A010:02
Over temperature
Internal terminal temperature is higher than 80°C (see
subindex
0xF80F:04 [
}
206]
)
BOOLEAN
RO
0x00 (0
dec
)
A010:03
Torque overload
Motor current is higher than the rated current
BOOLEAN
RO
0x00 (0
dec
)
A010:04
Under voltage
Motor supply voltage is 20% lower than the configured
nominal voltage (warning), or
Motor supply voltage is less than 8 V (error, see
0xA010:09 [
}
206]
)
BOOLEAN
RO
0x00 (0
dec
)
A010:05
Over voltage
Motor supply voltage is 10% higher than the configured
nominal voltage
BOOLEAN
RO
0x00 (0
dec
)
A010:06
Short circuit A
Short circuit in motor coil A
BOOLEAN
RO
0x00 (0
dec
)
A010:07
Short circuit B
Short circuit in motor coil B
BOOLEAN
RO
0x00 (0
dec
)
A010:08
No control power
Control voltage at the power contacts is less than 12 V
BOOLEAN
RO
0x00 (0
dec
)
A010:09
Misc error
Terminal initialization failed, or supply voltage is less than
8 V, or
internal terminal temperature is higher than 100°C (see
subindex
0xF80F:05 [
}
206]
)
BOOLEAN
RO
0x00 (0
dec
)
A010:0A
Configuration
CoE change has not yet been adopted into the current
configuration
BOOLEAN
RO
0x00 (0
dec
)
A010:11
Actual operation
mode
Current operating mode (relevant for activated automatic
mode, see 0x8012:01)
BIT4
RO
0x00 (0
dec
)
Index A020 POS Diag data Ch.1
Index
Name
Meaning
Data type
Flags
Default value
A020:0
POS Diag data Ch.1
Maximum subindex
UINT8
RO
0x06 (6
dec
)
A020:01
Command rejected
Travel command was rejected
BOOLEAN
RO
0x00 (0
dec
)
A020:02
Command aborted
Travel command was aborted
BOOLEAN
RO
0x00 (0
dec
)
A020:03
Target overrun
Target position was overrun in the opposite direction
BOOLEAN
RO
0x00 (0
dec
)
A020:04
Target timeout
The target window was not reached within the in-target
timeout
BOOLEAN
RO
0x00 (0
dec
)
A020:05
Position lag
The maximum following error was exceeded
BOOLEAN
RO
0x00 (0
dec
)
A020:06
Emergency Stop
An emergency stop was triggered (automatic or manual) BOOLEAN
RO
0x00 (0
dec
)
5.10.7
Vendor configuration data (device-specific)
Index F80F STM Vendor data
Index (hex) Name
Meaning
Data type
Flags
Default
F80F:0
STM Vendor data
Maximum subindex
UINT8
RO
0x08 (8
dec
)
F80F:01
PWM Frequency
DC link frequency (unit: 1 Hz)
UINT16
RO
0x7530
(30000
dec
)
F80F:02
Deadtime
Dead time for pulse width modulation
UINT16
RO
0x0505
(1285
dec
)
F80F:03
Deadtime space
Duty cycle limitation
UINT16
RO
0x0009 (9
dec
)
F80F:04
Warning temperature Threshold for temperature warning (unit: 1°C, see
subindex
0xA010:02 [
}
206]
)
INT8
RO
0x50 (80
dec
)
F80F:05
Switch off tempera-
ture
Switch-off temperature (unit: 1°C)
INT8
RO
0x64 (100
dec
)
F80F:06
Analog trigger point
Trigger point for AD conversion
UINT16
RO
0x000A (10
dec
)
F80F:07
Calibration offset A
Current measurement offset compensation for coil A (set
by the manufacturer)
INT16
RO
0x0000 (0
dec
)
F80F:08
Calibration offset B
Current measurement offset compensation for coil B (set
by the manufacturer)
INT16
RO
0x0000 (0
dec
)
Summary of Contents for EL7031
Page 1: ...Documentation EL70x1 Stepper Motor Terminals 4 4 2017 08 18 Version Date...
Page 2: ......
Page 6: ...Table of contents EL70x1 6 Version 4 4...
Page 48: ...Mounting and wiring EL70x1 48 Version 4 4 Fig 32 Other installation positions example 2...
Page 96: ...Commissioning EL70x1 96 Version 4 4 Fig 90 Incorrect driver settings for the Ethernet port...
Page 179: ...Commissioning EL70x1 179 Version 4 4 Index 7020 POS Outputs Ch 1...
Page 203: ...Commissioning EL70x1 203 Version 4 4 Index 7020 POS Outputs Ch 1...