Commissioning
EL70x1
145
Version: 4.4
K
v
factors
In the NC two proportional factors K
v
can be set under
"
Axis 1_Ctrl " in tab "Parameter". First select the
position controller
Type
with two P constants (with Ka) under the “NC Controller” tab. The two P constants
are for the
Standstill
range and for the
Moving
range (see Fig.
Setting the proportional factor K
V
). The factors
can be used to set the start-up torque and the braking torque to a different value than the drive torque. The
threshold value can be set directly below (Position control: Velocity threshold V dyn) between 0.0 (0%) and
1.0 (100%). Fig.
Velocity ramp with K
V
factor limit values
shows a speed ramp with thresholds of 30%. The
K
v
factor for Standstill (t
1
and t
3
) can be different than the Kv factor for Moving (t
2
). In this case the same
factor was used, since for stepper motors this function is less crucial than for DC motors.
Fig. 168: Speed ramp with K
V
factor limit values
Fig. 169: Setting the proportional factor K
V
Dead band for position errors
Microstepping can be used to target 200 * 64 = 12800 positions. Since the encoder can only scan 1024 * 4 =
4096 positions, positions between two encoder scan points may not be picked up correctly, in which case the
terminal will control around this position The dead band for position errors is a tolerance range within which
the position is regarded as "reached" (Fig.
Dead band for position errors
).
Summary of Contents for EL7031
Page 1: ...Documentation EL70x1 Stepper Motor Terminals 4 4 2017 08 18 Version Date...
Page 2: ......
Page 6: ...Table of contents EL70x1 6 Version 4 4...
Page 48: ...Mounting and wiring EL70x1 48 Version 4 4 Fig 32 Other installation positions example 2...
Page 96: ...Commissioning EL70x1 96 Version 4 4 Fig 90 Incorrect driver settings for the Ethernet port...
Page 179: ...Commissioning EL70x1 179 Version 4 4 Index 7020 POS Outputs Ch 1...
Page 203: ...Commissioning EL70x1 203 Version 4 4 Index 7020 POS Outputs Ch 1...