A TwinSAFE SC connection is added by adding an alias devices in the safety project and selecting TSC
(
TwinSAFE Single Channel
)
Fig. 107: Adding a TwinSAFE SC connection
After opening the alias device by double-clicking, select the Link button
next to
Physical Device,
in
order to create the link to a TwinSAFE SC terminal. Only suitable TwinSAFE SC terminals are offered in the
selection dialog.
Fig. 108: Creating a link to TwinSAFE SC terminal
The CRC to be used can be selected or a free CRC can be entered under the Connection tab of the alias
device.
Entry Mode
Used CRCs
TwinSAFE SC CRC 1 master
0x17B0F
TwinSAFE SC CRC 2 master
0x1571F
TwinSAFE SC CRC 3 master
0x11F95
TwinSAFE SC CRC 4 master
0x153F1
TwinSAFE SC CRC 5 master
0x1F1D5
TwinSAFE SC CRC 6 master
0x1663B
TwinSAFE SC CRC 7 master
0x1B8CD
TwinSAFE SC CRC 8 master
0x1E1BD