22
ENERGA 80-50
• Connecting convection set (option) to the convection air escape openings on the top
of the appliance:
°
Place the collar rings (2x or 4x) on the convection openings.
°
The convection air pipes must be made of non-fl ammable material which cannot
be distorted.
°
Attach the fl exible hose to the collar ring.
• Within a range of 30 cm either side and 50 cm above the escape openings in the
chimney, there must be no fl ammable materials (e.g. wooden ceiling, fi tted furniture).
• The convection casing of the built-in fi re must be covered all around with a 10-cm
thick layer of insulation (use of ceramic wool is permitted).
2.5 CONSTRUCTION REQUIREMENTS
Built-in fi res must be constructed such that the adapter from the chimney and convection
pipes can easily be cleaned.
There must be no electrical cables or gas pipes in the walls surrounding the area of the
fi replace.
In accordance with construction regulations (in Germany), combustion air pipes in
buildings with more than two inhabited fl oors containing piping and cabling running
through fi re walls must be fi tted in such a way that fi re and smoke cannot escape to
other fl oors or rooms.
2.6 HEAT-INSULATING MATERIALS
The heat-insulating materials to be used must meet specifi c quality standards.
Manufacturers of insulating materials quote an insulation number on the packaging
consisting of 10 numbers in accordance with the stipulations of AGI-Q132. Only those
insulating materials listed in the adjacent table 1 or alternatives approved (in Germany)
by DIBT may be used.
Summary of Contents for ENERGA 80-50
Page 2: ......
Page 3: ...3 ENERGA 80 50 ENERGA 80 50...
Page 4: ...4 ENERGA 80 50...
Page 6: ...6 ENERGA 80 50...
Page 8: ...8 ENERGA 80 50...
Page 10: ...10 ENERGA 80 50...
Page 31: ...31 ENERGA 80 50 Dismantle the steel bottom plate Dismantle the lower air slider...
Page 41: ......
Page 66: ...66 ENERGA 80 50 13 DIMENSIONS 13 1 ENERGA 80 50 Combustion air supply connection 125 mm...
Page 74: ...74 ENERGA 80 50...
Page 75: ......