LAYOUT DIAGRAM WITH VAPORISATION
Warnings
- The vaporizer is considered a dangerous point and should the
-
refore be situated at a
safe distance from any building.
- The electrical system must be AD-EP (anti-deflagration-explosion
proof).
- The L.P.G. pipelines must be made of SS steel with welded or
flanged joints NP 40 (nominal pressure 40 bar). Threaded joints
are prohibited.
Specific materials
1) Liquid recovery valve.
2) Liquid delivery cock with flow limiter.
3) Steel fitting with welded tang and copper washer.
4) 18 bar safety valve with welded steel fitting.
eventual emergency gas phase connection
tank reservoir
vaporize
1st stage reducer unit