Troubleshooting
9-7
9.6
Fault Correction
Use table 9.2 to troubleshoot the drive. If you cannot resolve the problem using this
table, contact Baldor-Reliance.
Table 9.2 – Corrective Actions
Keypad
Display
Fault
Cause
Remedy
Overcurrent
•
Accel/Decel time is
too short compared to
the inertia of the load.
•
Increase the
Accel/Decel time.
•
Load is greater than
the drive rating.
•
Replace the inverter
with appropriate
capacity
•
Inverter enabled when
the motor is rotating.
•
Resume operation
after stopping the
motor or use H22
(Speed search).
•
Output short circuit or
ground fault has
occurred.
•
Check output wiring.
•
Mechanical brake on
the motor is operating
incorrectly.
•
Check the mechanical
brake
ATTENTION:
When an overcurrent fault occurs,
the cause of the fault must be corrected before
operation is restarted. Failure to observe this
precaution could result in damage to, or
destruction of, the IGBT.
Ground fault
current
•
Ground fault has
occurred in the output
wiring of the drive.
•
Check the wiring
between the drive and
the motor.
•
The insulation of the
motor is damaged.
•
Replace the motor.
Inverter
Overload
•
Load is greater than
the drive rating.
•
Upgrade the capacity
of motor and drive or
reduce the load.
Overload trip
•
Torque boost scale is
set too large.
•
Reduce torque boost
scale.
Summary of Contents for VS1MD
Page 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Page 5: ...4 VS1MD AC Drive User Manual...
Page 11: ...1 2 VS1MD AC Drive User Manual...
Page 27: ...4 8 VS1MD AC Drive User Manual...
Page 103: ...7 58 VS1MD AC Drive User Manual...
Page 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Page 133: ...8 30 VS1 MD AC Drive User Manual...
Page 143: ...9 10 VS1 MD AC Drive User Manual...
Page 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Page 155: ...B 10 VS1MD User Manual...
Page 167: ...VS1MD User Manual...
Page 168: ......
Page 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...