7-44
VS1MD AC Drive User Manual
H19
Phase Loss Protection
Range:
0 - 3n
Default:
0
Access
Tunable
Setting H19 to a value other than 0 enables Phase Loss Protection.
Output Phase Loss: Inverter output is shut off in the event of more than one
phase loss among U, V and W.
Input Phase Loss: Inverter output is blocked at the event of more than one
phase loss among R, S and T. If there is no input phase loss, output is shut
off when it is time to replace the DC link capacitor.
Note: Set P32 – Motor Rated Current correctly. If the actual motor rated
current and the value of P32 are different, output phase loss protection
function may not activate correctly.
0 = Not Used
1 = Output phase loss protection
2 = Input phase loss protection
3 = Input/output phase loss protection
H20
Power On Start
Range:
0 - 1
Default:
0
Access
Tunable
See also:
P38
Setting H20 = 1 enables power on start. This parameter is activated when
P38 – Drive Mode is set to 1 or 2 (Run/Stop via Control Terminal). Motor
will accelerate after AC power is applied and a Forward Run (FX) or
Reverse Run (RX) terminal is ON.
This parameter is inactive if P38 – Drive Mode is set to Keypad or RS485.
ATTENTION:
Particular attention must be directed to this function due to
potential hazard as motor starts to run suddenly upon applying AC input
power.
Run
command
Frequency
Input voltage
When H20 is 0
When H20 is 1
Summary of Contents for VS1MD
Page 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Page 5: ...4 VS1MD AC Drive User Manual...
Page 11: ...1 2 VS1MD AC Drive User Manual...
Page 27: ...4 8 VS1MD AC Drive User Manual...
Page 103: ...7 58 VS1MD AC Drive User Manual...
Page 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Page 133: ...8 30 VS1 MD AC Drive User Manual...
Page 143: ...9 10 VS1 MD AC Drive User Manual...
Page 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Page 155: ...B 10 VS1MD User Manual...
Page 167: ...VS1MD User Manual...
Page 168: ......
Page 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...