C-8
VS1MD User Manual
C.6.2.10 Action Request for Monitor Register:
Request to read address registered by monitor register.
Total bytes = 7
C.6.2.11Acknowledge Response:
Total bytes = 7 + n * 4 = Max 39
C.6.2.12Negative Response:
Total bytes = 9
C.6.2.13Error codes
ENQ
Drive No
CMD
SUM
EOT
05h
“01” to “1F”
“Y”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
1 byte
ACK
Drive No
CMD
Data
SUM
EOT
06h
“01” to “1F”
“Y”
“XXXX…”
“XX”
04h
1 byte
2 bytes
1 byte
n * 4 bytes
2 bytes
1 byte
NAK
Drive No
CMD
Error code
SUM
EOT
15h
“01” to “1F”
“Y”
“**”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Error code
Description
“IF”
When master is sending codes other than Function code (R, W, X,
“IA”
When parameter address does not exist
“ID”
When Data value exceeds its permissible range during ‘W’ (Write).
“WM”
When the specific parameters cannot be written during
‘
W’ (Write).
(For example, in the case of Read Only, Write disabled during Run)
“FE”
When frame size of specific function is not correct and Checksum
Summary of Contents for VS1MD
Page 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Page 5: ...4 VS1MD AC Drive User Manual...
Page 11: ...1 2 VS1MD AC Drive User Manual...
Page 27: ...4 8 VS1MD AC Drive User Manual...
Page 103: ...7 58 VS1MD AC Drive User Manual...
Page 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Page 133: ...8 30 VS1 MD AC Drive User Manual...
Page 143: ...9 10 VS1 MD AC Drive User Manual...
Page 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Page 155: ...B 10 VS1MD User Manual...
Page 167: ...VS1MD User Manual...
Page 168: ......
Page 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...