7-48
VS1MD AC Drive User Manual
H37
Load Inertia Rate
Range:
0=Load inertia rate is less than 10 times that of motor
inertia
1=Load inertia rate equal to approximately 10 times the
motor inertia.
2=Load inertia rate is more than 10 times that of motor
inertia.
Default:
0
Access
Configurable
See also:
F8-F11, H40
Select range according to the connected inertia in relationship to the motor
inertia.
H39
Carrier Frequency Select
Range:
2-15 [kHz]
Default:
2
Access
Tunable
This parameter affects the audible sound of the motor, noise emission form
the inverter, inverter temperature, and leakage current. If the set value is
higher, the inverter sound is more quiet, but the noise from the inverter and
leakage current will be increased.
H40
Control Mode Select
Range:
0=Volts/Frequency Control
1=Slip Compensation Control
2=PID Feedback Control
3=Sensorless Vector Control
Default:
0
Access
Configurable
This parameter selects the control mode for the operation of the drive. See
the following description of control method and the corresponding
parameters for adjustment to each.
Summary of Contents for VS1MD
Page 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Page 5: ...4 VS1MD AC Drive User Manual...
Page 11: ...1 2 VS1MD AC Drive User Manual...
Page 27: ...4 8 VS1MD AC Drive User Manual...
Page 103: ...7 58 VS1MD AC Drive User Manual...
Page 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Page 133: ...8 30 VS1 MD AC Drive User Manual...
Page 143: ...9 10 VS1 MD AC Drive User Manual...
Page 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Page 155: ...B 10 VS1MD User Manual...
Page 167: ...VS1MD User Manual...
Page 168: ......
Page 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...