7-14
VS1MD AC Drive User Manual
11 = DC brake during start: DC voltage will be applied to the motor
windings at a level set by DC Brake Start Voltage (F12) for as long as the
digital input is closed. See also F12 and F13 – Starting DC brake
parameters.
12 = 2
nd
motor select: When input is present, the drive configures itself for
a second set of motor settings defined in 2
nd
motor operation parameters
(H81 to H90).
13 = Reserved: Reserved
14 = Reserved: Reserved
15 = Frequency increase (UP): Increases the frequency reference to the
drive after a run command. Frequency is saved to parameter F64 on a stop
command if F63 = 1 ‘save up/down frequency’.
16 = Frequency decrease (DOWN): decreases the frequency reference to
the drive after a run command. Frequency is saved to parameter F64 on a
stop command if F63 = 1 ‘save up/down frequency’.
17 = 3-wire operation: Select to define a digital input for 3-wire control.
Inputs defined as forward (FX) and reverse (RX) are momentary inputs and
opening the input defined as 3-wire operation will stop the drive. For both
2-wire and 3-wire control, P38 – Drive Mode should be set to a 1 for normal
operation.
00000000
00000000
Voltage
Run
command
F12
P3
P1
P2
P8
CM
FX :
t1 = 0
RX :
t2 = 1
3-Wire :
t8 = 17
FX
RX
Frequency
P8 (3-Wire)
t
Summary of Contents for VS1MD
Page 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Page 5: ...4 VS1MD AC Drive User Manual...
Page 11: ...1 2 VS1MD AC Drive User Manual...
Page 27: ...4 8 VS1MD AC Drive User Manual...
Page 103: ...7 58 VS1MD AC Drive User Manual...
Page 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Page 133: ...8 30 VS1 MD AC Drive User Manual...
Page 143: ...9 10 VS1 MD AC Drive User Manual...
Page 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Page 155: ...B 10 VS1MD User Manual...
Page 167: ...VS1MD User Manual...
Page 168: ......
Page 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...