Parameter Descriptions
7-39
F64
Saved up/down frequency
Range:
n/a
Default:
0.00
Access
Read Only
See also:
t1-t8, F63
Notes:
F64 viewable when F63 = 1 (Save up/down frequency)
Stores the up/down frequency if F63 = 1 before the drive stops or
decelerates.
F65
Start Frequency
Range:
0.10 to 10.00 [Hz]
Default:
0.5
Access
Configurable
The drive starts to output its voltage at this frequency. It is the low frequency
limit.