INTRODUCTION
I-E96-315B
C - 1
APPENDIX C - DIGITAL INPUT TERMINATION
MODULE (NIDI01)
INTRODUCTION
The IMHSS02 uses an NIDI01 termination module to terminate
I/O signals. Jumpers on the termination module configure the
I/O signals. The hydraulic servo slave (HSS) module provides
one digital and four analog outputs, and three digital and two
analog inputs for control of hydraulic actuators.
shows the jumper settings and their location on the
NIDI01 circuit board. As shown in Figure
, jumpers 1
through 9 remain intact (shorted), jumper 10 is open. Figure
shows the terminal assignment and polarity for each of the
I/O signals. Refer to this figure when connecting field wiring to
the NIDI01. Figure
shows how to connect the termination
cable from the NIDI01 to the IMHSS02.
Figure C-1. HSS Jumper Settings and Location on the NIDI01
TP25315A
TERMINAL 1
TERMINAL 32
J1
P1 CARD EDGE
CONNECTOR FOR
NKTM01 OR
NKTU02/12 CABLE
J10
P1
NIDI01
J1-J10 JUMPER SETTINGS