INSTALLATION
INITIAL SWITCH SETTINGS
I-E96-315B
3 - 5
Switch S3 - Dither Oscillator Frequency
Switch S3 is a two position switch that determines the dither
oscillator frequency. Set the dither oscillator frequency to the
value the manufacturer of the servo valve recommends. To set
the dither oscillator frequency:
1. Refer to the servo valve specifications for the recommended
dither oscillator frequency.
2. Refer to Table
for switch settings and set S3
accordingly.
Table 3-2. S2 Controller Gain
Close Switch
For a Gain of
User Setting
1
20.50
2
18.25
3
15.05
4
13.10
5
10.00
6
5.00
7
2.01
8
1.10
NOTE: Closing a switch position will select the corresponding gain.
Close only one switch at a time. All other switch positions must remain
open. There are eight possible controller gains. For example: For a gain
of 5.00, leave switch position 6 CLOSED and all others OPEN.
1 = Open (off), 0 = Closed (on)
Table 3-3. S3 Dither Oscillator Frequencies
Switch Position
Frequency
User Setting
1
2
Closed
Open
300 Hz (high)
Open
Closed
200 Hz (low)
NOTE: Do not leave both switches open or closed; circuit will not func-
tion properly.
1 = Open (off), 0 = Closed (on)