INSTALLATION
INITIAL SWITCH SETTINGS
I-E96-315B
3 - 3
6. Connect a 14 AWG wire from E1 or E2 to a source of +24
VDC within the cabinet.
Termination Module Installation
1. Configure the jumpers on the termination module.
2. Connect one end of NKTM01 or NKTU02/12 cable to the
rear of the termination mounting unit (TMU) slot for the termi-
nation module. Connect the other end of the cable to the rear
of the MMU slot (backplane) for the HSS.
3. Insert the termination module in the assigned slot of the
TMU leaving the terminals next to the faceplate exposed.
4. Connect the wiring from the servo valve, linear variable dif-
ferential transformer and digital I/O to the termination mod-
ule.
5. Push the module into the TMU until it seats in the termina-
tion module connector.
INITIAL SWITCH SETTINGS
The HSS has seven switches that the user must configure.
Switch settings are application dependent. The information in
this section covers the switch settings needed for initial instal-
lation. Complete the steps in this part of the installation proce-
dure to prepare the module for calibration and tuning.
Switch S1 - Slave Expander Bus Address
Switch S1 is an eight position dipswitch. The user sets the
slave expander bus address at any unused address value from
0 to 63. Switch positions 1 and 2 must always be in the
CLOSED position. Use positions 3 through 8 to set the
address. Table
shows examples of switch settings for the
slave expander bus address. See Figure
for the location of
S1 on the HSS module. Record the slave expander bus address
in the user setting column.
CAUTION
Only qualified personnel should configure these switches.
Damage or misoperation could occur if switches are improp-
erly configured.
ATTENTION
La configuration de ces interrupteurs ne devrait etre effectuee
que par un personnel qualifie. Des dommages ou une mau-
vaise operation pourraient resulter d'une mauvaise configura-
tion des interrupteurs.