INSTALLATION
CONFIGURATION
3 - 8
I-E96-315B
®
2. Check the slave expander bus dipshunt socket on the
backplane of the MMU. The dipshunt must be installed with all
pins shorted. This provides a communication path from the
master module to the slave module.
3. Align the top and bottom edges of the circuit card with the
top and bottom rails of the assigned slot in the MMU.
4. Slide the module into the slot. Push until the module is
seated in the backplane connector. Turn the two thumbscrews
on the faceplate a half turn until the module locks in place.
CONFIGURATION
To work with the HSS, the MFP or MFC must have function
code 150 in its configuration. To configure the processor or
controller module:
1. Refer to the
Function Code Application Manual
for con-
figuration instructions.
2. Configure the processor or controller module with function
code 150, specifications S1 and S2.
3. Leave the remaining specifications at their default value.
They require modification during the module calibration
procedure.
Table 3-7. S7 LVDT Oscillator Frequency
Switch Position
Frequency
User Setting
1
2
Open
Open
1000 Hz
Open
Closed
2500 Hz
Closed
Open
10 kHz
NOTE: 1 = Open (off), 0 = Closed (on)