TROUBLESHOOTING
ON-LINE FAILURE
6 - 4
I-E96-315B
®
Figure 6-1. Off-Line Failure Troubleshooting Flowchart
(Page 3 of 3)
HSS
OPERATING?
YES
NO
DONE
TU
DIPSHUNTS
SET?
TERMINAL
CONNECTIONS
CORRECT?
NO
NO
HSS
OPERATING?
YES
NO
HSS
OPERATING?
YES
NO
YES
YES
CORRECTLY
INSTALL
DIPSHUNTS
CONNECT FIELD
WIRING TO TU
TERMINALS
TP25256A
A2
B2
SERVO VALVE
INSTALLED
PROPERLY?
LVDT,
ACTUATOR
INSTALLED
PROPERLY?
NO
NO
YES
YES
CHECK SERVO
VALVE AND CABLE
INSTALLATION
CHECK ACTUATOR
AND LVDT
INSTALLATION
AND CABLE
CONTACT BAILEY
TECHNICAL
SUPPORT
REPLACE HSS
MODULE