INSTALLATION
SETUP/INSTALLATION
3 - 2
I-E96-301B
®
4. Use the original packing material or container to store the
module.
5. Store the module in a place with clean air; free of extremes
of temperature and humidity.
SETUP/INSTALLATION
Before applying power to the IMASI03, make these checks:
1. Check that the module address is set correctly.
2. Check that the jumpers on the module are set correctly.
3. Be sure the dipshunts in the MMU's slave expander bus
are installed correctly.
4. Check that the jumpers on the termination devices are set
correctly.
5. Verify I/O cabling connections.
6. Verify there is sufficient logic and field power for the mod-
ules in the MMU.
Address Selection Switch (SW1)
The IMASI03 must have an address to communicate with the
MFP. The IMASI03 can have one of 64 addresses (address 0 to
63) on the slave expander bus. This address identifies the slave
to the master module and must be the same as the address set
in the master module configuration data (function code 215
and 216 specification 1).
Set the address with the eight position address dipswitch
(SW1), shown in Figure 3-1. The six right switch positions (3
Figure 3-1. Address Select Switch (SW1)
IMASI03
P1
P3
P2
TP35254A
SW1
OPEN
7
6
2 3 4 5
1
8
1
2
3
4
5
8
6
7
OPEN
MODULE
ADDRESS
MSB
LSB
NOTE: SET CONTACTS 1 AND 2
TO CLOSED. SET THE ADDRESS
ON CONTACTS 3 THROUGH 8.
= OFF = OPEN = LOGIC 1
= ON = CLOSED = LOGIC 0
EDGE
CONNECTORS