NTAI06 TERMINATION UNIT CONFIGURATION
CONFIGURING INPUTS
I-E96-301B
B - 3
CONFIGURING INPUTS
This section contains figures of revision A and revision B
IMASI03 termination units.
•
Figure
shows the jumper locations and terminal
assignments for revision A hardware. Check jumpers
before installing the NTAI06. Figure
shows the jumper
locations and terminal assignments for revision B hard-
ware. Check jumpers before installing the NTAI06.
•
Figure
shows a typical input circuit and the jumpers
used for each input.
•
shows field input termination examples for revi-
sion A and B hardware.
•
shows IMASI03 input examples.
•
shows the cabling for the IMASI03. The NKAS01
(or NKAS11) cable connects the termination unit to the
IMASI03. The NKAS01 cable has PVC insulation and is
rated for 80
o
C (0 to 176
o
F) at 300 V (UL rated type CL2).
The NKAS11 cable has non-PVC insulation and is rated for
90
o
C (0 to 194
o
F) at 300 V (UL rated type PLTC).