INTRODUCTION
I-E96-301B
3 - 1
SECTION 3 - INSTALLATION
INTRODUCTION
This section explains what to do before putting the Universal
Analog Input Slave Module (IMASI03) into operation.
DO NOT
PROCEED
with the installation and operation until you read,
understand and do the steps in the order in which they appear.
Refer to
for termination device
wiring instructions. Refer to
to configure the
IMASI03.
SPECIAL HANDLING
NOTE: Always use Bailey's Field Static Kit (P/N 1948385A2 - wrist
strap, ground cord assembly, alligator clip) when working with mod-
ules. The kit connects a technician and the module to the same
ground point to prevent damage to the module by electrostatic
discharge.
This device uses metal oxide semiconductor (MOS) devices that
require special precautions during shipping and handling.
Static discharge, improper grounding, and careless handling
can damage these devices. To help reduce the chance of dam-
age, follow these procedures:
1. Keep the module in its special antistatic bag until ready to
install it. Save the antistatic bag for future use.
2. Ground the antistatic bag before opening it.
3. Make sure all devices to which the module connects are
properly grounded before connection.
4. Avoid touching the circuitry when handling the module.
NOTE: Wear the grounding strap from the field static kit when
removing or installing the module to change switch settings.
UNPACKING AND INSPECTION
These are steps to follow for general handling:
1. Examine the module to make sure that no damage has
occurred in transit.
2. Notify the nearest Bailey Controls sales/service office of
any damage.
3. File a claim for any damage with the shipping company
that handled the shipment.