background image

Table of Contents

Page

I-E96-301B   

iii

SECTION 1 - INTRODUCTION ....................................................................................................1-1

OVERVIEW ..................................................................................................................1-1
INTENDED USER .........................................................................................................1-1
MODULE DESCRIPTION ..............................................................................................1-1
FEATURES...................................................................................................................1-2
INSTRUCTION CONTENT .............................................................................................1-4
HOW TO USE THIS MANUAL .......................................................................................1-4
GLOSSARY OF TERMS AND ABBREVIATIONS .............................................................1-5
REFERENCE DOCUMENTS..........................................................................................1-7
NOMENCLATURE ........................................................................................................1-7
SPECIFICATIONS .........................................................................................................1-8

SECTION 2 - DESCRIPTION AND OPERATION........................................................................2-1

INTRODUCTION ...........................................................................................................2-1
FUNCTIONAL OPERATION ...........................................................................................2-1
BLOCK DIAGRAM ........................................................................................................2-1

Isolation Amplifier..................................................................................................2-2
Input Multiplexer (MUX).........................................................................................2-2
Analog to Digital Conversion ..................................................................................2-2
Microcontroller and Memory ..................................................................................2-3
Cold Junction Reference ........................................................................................2-3
Switch Settings ......................................................................................................2-4
On-Board Indicators ..............................................................................................2-4

SLAVE EXPANDER BUS ...............................................................................................2-4

Slave Expander Bus Interface ................................................................................2-5
Data Values ...........................................................................................................2-5
Termination Units ..................................................................................................2-5
Function Codes......................................................................................................2-5

AUTOMATIC ADJUSTMENTS AND CORRECTIONS.......................................................2-6

Input Processing ....................................................................................................2-6
Point Value Calculation..........................................................................................2-6
Input Calibration ...................................................................................................2-7
Lead Wire Resistance Adjustment ..........................................................................2-7
Cold Junction Compensation .................................................................................2-7
User Gain and Offset Adjustment ...........................................................................2-8
Engineering Units Conversion ................................................................................2-8
Automatic Calibration ............................................................................................2-9
Field Calibration ....................................................................................................2-9

INPUT CALIBRATION ...................................................................................................2-9
SECURITY AND INTEGRITY CHECKS ...........................................................................2-9

Diagnostics Run on Reset ......................................................................................2-9
Diagnostics Run in Diagnostic Mode ....................................................................2-10
Diagnostics Run During Normal Operation ..........................................................2-10
Expander Bus Communication Security ...............................................................2-10
Open Input Detection...........................................................................................2-10
Alarm and Exception Reporting ............................................................................2-10

ON-LINE CONFIGURATION ........................................................................................2-11
LOGIC POWER...........................................................................................................2-11

Summary of Contents for infi 90 IMASI03

Page 1: ...Process Control and Automation Solutions from Elsag Bailey Group E96 301 Universal Analog Input Slave Module IMASI03...

Page 2: ...UIPEMENTS LECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FR QUENCE RADIO DES PR CAUTIONS DEVRONT TRE PRISES LORS DE L UTILISATION DU MAT RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PR...

Page 3: ...g signal interface for the Multi Function Processor Module with variable ana log to digital conversion resolution up to a maximum of 24 bits This instruction explains the slave module features specifi...

Page 4: ...rough 6 6 Original 6 7 15 December 1994 6 8 through 6 11 Original 7 1 Original 8 1 Original 9 1 Original A 1 through A 13 Original B 1 through B 9 Original C 1 through C 14 Original Index 1 through In...

Page 5: ...Hazard During Maintenance Disconnect power or take precautions to insure that contact with energized parts is avoided when servicing Special Handling This module uses Electrostatic Sensitive Devices...

Page 6: ...ion ou prendre les pr cautions pour viter tout contact avec des composants sous tension durant l entretien Precautions de Manutention Ce module contient des composantes sensibles aux decharges electro...

Page 7: ...Board Indicators 2 4 SLAVE EXPANDER BUS 2 4 Slave Expander Bus Interface 2 5 Data Values 2 5 Termination Units 2 5 Function Codes 2 5 AUTOMATIC ADJUSTMENTS AND CORRECTIONS 2 6 Input Processing 2 6 Po...

Page 8: ...6 Test Equipment Required 4 6 Individual Channel Calibration 4 7 SECTION 5 OPERATING PROCEDURES 5 1 INTRODUCTION 5 1 START UP 5 1 OPERATION 5 1 ON BOARD INDICATORS 5 1 SECTION 6 TROUBLESHOOTING 6 1 I...

Page 9: ...TION B 1 Cold Junction Reference Input B 1 Configuring Inputs B 1 CONFIGURING INPUTS B 3 APPENDIX C FUNCTION CODE DEFINITIONS C 1 INTRODUCTION C 1 ENHANCED ANALOG SLAVE DEFINITION FUNCTION CODE FC 215...

Page 10: ...ns for Revision A Hardware NIAI05 A 5 A 2 Jumper Locations for Revision B Hardware NIAI05 A 6 A 3 Terminal Assignments for Revision A Hardware NIAI05 A 7 A 4 Terminal Assignments for Revision B Hardwa...

Page 11: ...one slot in an INFI 90 Module Mounting Unit MMU Two captive latches on the module faceplate secure it to the MMU The slave module has three card edge connectors for external sig nals and power P1 P2 a...

Page 12: ...s and isolates up to 16 analog input signals The IMASI03 converts analog signals to digital values adds compensation and corrections as needed and provides dig ital values to the MFP through the slave...

Page 13: ...on during normal operation to compensate for component aging and temperature drift No user calibration is ever required Engineering units conversion to degrees C or F is automat ically calculated on a...

Page 14: ...test the IMASI03 Maintenance Has a schedule for taking care of the IMASI03 This schedule can be used for all the modules in the MMU Repair Replacement Procedures Contains the cautions and steps for re...

Page 15: ...t circuit from damage up to a maximum specified voltage level Also indicates the ability to reject the common mode voltage by a specified amount in units of dB at a specific frequency such as 60 Hz Co...

Page 16: ...cage that provides electrical and communication support for INFI 90 modules MSB Most Significant Bit the bit of a binary number that carries the most numerical weight Normal Mode Rejection Indicates t...

Page 17: ...tput connection between plant equipment and the INFI 90 process modules The termination unit is mounted flat on a Field Termination Panel FTP Number Description I E93 900 20 Function Code Application...

Page 18: ...10 Ohm copper Chinese 53 Ohm copper Millivolt 100 mV to 100 mV o to 100 mV High Level 1 5 VDC 0 5 VDC 0 10 VDC 10 VDC to 10 VDC or user specified range within 10 VDC and 10 VDC Current 4 20 mA system...

Page 19: ...ge FSR 500 Ohms Cold Junction Reference Accuracy 0 5 C Software Temperature Linearization Accuracy 0 1 C Resolution Error Two Standard Deviations From Mean Typical Noise Reading Stability Bits Percent...

Page 20: ...in steps of two over full scale resolution Temperature Effect 0 70 C 0 003 of full scale range per degree C maximum Power Supply Effect Over Operating Range 15 Volt Supplies 0 003 of full scale range...

Page 21: ...C 131o F noncondensing 5 to 45 at 70o C 158o F noncondensing Atmospheric Pressure Sea level to 3 km 1 86 miles 86 kPa to 108 kPa Air Quality Noncorrosive Mounting Occupies a single slot in a standard...

Page 22: ...is isolation amplifier also contains references used for on line calibration Each channel accepts voltage and resistance inputs Resis tance measurements are made by digitizing the voltage drop created...

Page 23: ...put signal is ready to be digitized All the inputs including the references and cold junction input are multiplexed through the same analog to digital converter as shown in Figure 2 1 Analog to Digita...

Page 24: ...bus data through dual port RAM DPRAM Cold Junction Reference The IMASI03 measures the cold junction RTDs on the slave s termination device This results in an accurate reading of the ambient temperatur...

Page 25: ...the IMASI03 module occurs For example if power up diagnostics fail Show solid red for a power fail interrupt PFI Show pass fail of diagnostic routines when in diagnostic mode refer to Section 6 SLAVE...

Page 26: ...ering units The slave sends a status indication to the MFP master for each input channel This status indicates any hardware errors and channel configuration errors detected by the slave Termination Un...

Page 27: ...ast as the conversion time allows In addition to the active input channels the built in cold junc tion reference and the reference values for drift correction are digitized during normal input scannin...

Page 28: ...resistance depends upon the input channel circuitry used for a particular input signal type For millivolt and ther mocouple inputs lead wire resistance is equal to the series resistance of the and le...

Page 29: ...er gain and off set values can be set and reset using function code 217 Once defined user gain and offset values remain in NVRAM and are not lost when module power is interrupted For more informa tion...

Page 30: ...area If field calibration does not provide the desired results the fac tory calibration data can be restored Using Function code 217 to change the gain or offset values per channel and type can compen...

Page 31: ...afeguard against an A D converter failure which would halt input scan ning Input circuits are monitored for open circuits Any errors are reported to the master MFP through the slave module sta tus Cer...

Page 32: ...for a short period the status remains unchanged during this period This hold time is based on the number of channels that were changed during on line configuration as well as the resolution specified...

Page 33: ...MOS devices that require special precautions during shipping and handling Static discharge improper grounding and careless handling can damage these devices To help reduce the chance of dam age follow...

Page 34: ...sufficient logic and field power for the mod ules in the MMU Address Selection Switch SW1 The IMASI03 must have an address to communicate with the MFP The IMASI03 can have one of 64 addresses address...

Page 35: ...ddr 3 4 5 6 7 8 Addr 3 4 5 6 7 8 0 1 2 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 1 0 1 32 33 34 35 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 1 0 1 4 5 6 7 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 0 0 1 1 0 1...

Page 36: ...er Position Jumper Number Current Thermocouples Low Level Voltage High Level Voltage 1 2 J1 J32 Analog Input 1 through Analog Input 16 3 Wire RTD 2 3 J1 J32 Analog Input 1 through Analog Input 16 Tabl...

Page 37: ...the termination module unit to the MMU backplane To do this insert the con nector into the backplane slot in the same slot as the one assigned to the slave module The latches should snap securely into...

Page 38: ...TAI06 termination unit for termination A single NKAS02 or NKAS12 is used to connect the IMASI03 to two NIAI05 termination modules The NTAI06 requires an NKAS01 or NKAS11 to connect to the IMASI03 The...

Page 39: ...MASI03 Cable Connections TP35256A P1 P3 J3 J2 J1 P2 NKAS01 11 SEE NOTE ANALOG SLAVE TERMINATION UNIT CABLE NTAI06 CHANNELS 11 16 CHANNELS 1 10 IMASI03 FIELD WIRING NOTE NKAS01 HAS PVC INSULATION SPECI...

Page 40: ...r field calibration although it should not be required CONFIGURING INPUTS Configure the IMASI03 by setting the specifications in function code 215 and 216 in the master MFP One function code 215 is re...

Page 41: ...e terminal blocks Each slave configured for a thermocouple input requires a cold junction reference Each slave can only have one cold junction reference for up to 16 thermocouple inputs The exception...

Page 42: ...lock The command errors are provided as an output N 4 of this function block It reflects the status of the most recently issued calibration command The status of a channel field calibration is also re...

Page 43: ...lave input reading of that channel and type Field calibrating all 16 channels for all three input types on a slave is a lengthy procedure that may require up to four hours to complete when done proper...

Page 44: ...o 11 calibration points may be identified to adjust for non linear components in the input circuitry Precision voltage val ues are required for low level thermocouple and high level input field calibr...

Page 45: ...el a low level or a 3 wire RTD input The high level low level and 3 wire RTD inputs can be field cal ibrated with this procedure We recommend checking the accuracy of the channel within each of the sp...

Page 46: ...nge calibration for chan nel one on the IMASI03 referenced by the function code 215 at block address 100 S4 of function code 216 must also be set to any of the thermocouple or millivolt types This exa...

Page 47: ...nction code 215 in the configuration 6 Allow the slave to warm up for at least 15 minutes 7 Put the MFP in execute mode 8 Set the FC 217 block for the required specifications After each calibration co...

Page 48: ...the 15 second settling time 12 Tune the FC 217 block to the next higher value in the cali bration range In this example tune specification 5 to a perform point calibration S1 2 b the slave referenced...

Page 49: ...e operation can be verified by checking FC 217 blocks N 1 and N 4 for a zero value If the enable was unsuccessful an error code will appear in the FC 217 blocks N 1 and N 4 which can aid in troublesho...

Page 50: ...n ever the MFP sends new configuration data This interrupt causes the slave to read the configuration data and initialize its input handling conversion and compensation calculations Once configured by...

Page 51: ...der bus communication is lost if the MFP is removed Show solid red if a fatal failure of the IMASI03 module occurs For example if power up diagnostics fail Show solid red for a power fail interrupt PF...

Page 52: ...mode from execute mode Blink green if slave expander bus communication is lost if the MFP is removed Show solid red if a fatal failure of the IMASI03 module occurs For example if power up diagnostics...

Page 53: ...IMASI03 Error Types Module Problem Report Type 12 Error Type Error Description Slave Error Corrective Actions 14 Calibration 0EH problem report from FC 216 Channel 1 16 Disabled Remove IMASI03 and in...

Page 54: ...inue to function properly 2 Calibration Error 02H problem report from FC 215 Cold Junction Reference Error 2 Calibration Error 02H problem report from FC 216 Channel 1 16 Reference Error Remove IMASI0...

Page 55: ...to 1 the MFP will continue to execute if function code 215 detects an error A module problem report can be requested in order to get specific information about any slave error indicated in module sta...

Page 56: ...status refer to the Multi Function Processor product instruction manual 5 Configuration Error Undefined Input The indicated FC 215 or FC 216 detected a function code channel link error Verify FC 215 s...

Page 57: ...truction manual for the operator interface being used The master module generates a local I O error in the module status if the slave expander bus is not connected between the slave module and the mas...

Page 58: ...001000 00010000 00100000 1 Module addresses 2 for the slave 4 expander bus test 8 16 32 10000000 1x2000001 Dipswitch test Watchdog timer test 1x2 000100 1x2000101 1x2000110 1x2 000111 CPU test Timer t...

Page 59: ...e if all tests are selected the LED will repeat a sequence of being on for ten seconds and off for ten seconds Dipswitch Configurable Diagnostics The diagnostic tests check these slave components Slav...

Page 60: ...If the All Tests Mode is suc cessful go to the Universal Slave Bus Test If the slave is failing the All Tests Mode and the halt display on error bit is set the status LED will begin blinking an error...

Page 61: ...ion shows the pin connections for the IMASI03 Check the signals on the pins and compare them to the tables The slave module has three connection points for external signals and power P1 P2 and P3 Tabl...

Page 62: ...OM1 28 COM2 4 IN2 29 IN2 5 IN3 30 IN3 6 COM3 31 COM4 7 IN4 32 IN4 8 IN5 33 IN5 9 COM5 34 COM6 10 IN6 35 IN6 11 IN7 36 IN7 12 COM7 37 COM8 13 IN8 38 IN8 14 IN9 39 IN9 15 COM9 40 COM10 16 IN10 41 IN10 1...

Page 63: ...are the same as the failed module This section contains a sched ule to help take care of the system hardware Refer questions to your local Bailey Controls service office MAINTENANCE SCHEDULE Do the ta...

Page 64: ...unlatch the module It is unlatched when the slots on the latches are vertical and the open end of the slots face away from the center of the module 2 Gently slide the module out of the MMU 3 Configure...

Page 65: ...calling in to order parts 1 Part description part number and quantity 2 Model and serial numbers 3 Bailey instruction manual number page number and fig ure that describe the part When ordering standa...

Page 66: ...e NKAS02 or NKAS12 connec tor cable Channel designation labels are provided with each NIAI05 This allows the user to configure one NIAI05 as the J2 termina tion module for channels 1 through 8 and con...

Page 67: ...configurations for the NIAI05 Table A 3 describes the NIAI05 input types Table A 1 NIAI05 Input Types Input Type Signal Type Thermocouple E J K L N 14 AWG N 28 AWG R S T U Chinese E Chinese S Millivo...

Page 68: ...imiting resistor on NIAI05 modules with revision A hardware revision B hardware replaces the resistor with a fuse The minus input terminal connects to a precision resistor that generates a single ende...

Page 69: ...r each input Figure A 5 shows a typical input circuit for the revision A hardware NIAI05 Figure A 6 shows a typical input circuit for the revision B hardware NIAI05 Figure A 7 shows revision A hardwar...

Page 70: ...30 1 1 3 3 2 2 J5 J21 J13 J29 1 1 3 3 2 2 J4 J20 J12 J28 1 1 3 3 2 2 J3 J19 J11 J27 1 1 3 3 2 2 J8 J24 J16 J32 JUMPER INSTRUCTIONS SINGLE ENDED VOLTAGE DIFFERENTIAL VOLTAGE SYS POWERED 4 20 mA EXT POW...

Page 71: ...1 3 3 2 2 J5 J21 J13 J29 1 1 3 3 2 2 J4 J20 J12 J28 1 1 3 3 2 2 J3 J19 J11 J27 1 1 3 3 2 2 J8 J24 J16 J32 JUMPER INSTRUCTIONS SINGLE ENDED VOLTAGE DIFFERENTIAL VOLTAGE SYS POWERED 4 20 mA EXT POWERED...

Page 72: ...1 1 2 3 32 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 1 2 I O COM I O COM 24 VDC 24 VDC ANALOG INPUT TERMINAL NUMBER J2 ANALOG INPUT TERMINAL NUMBER J3 TP35261A C C...

Page 73: ...ANNEL 9 INPUT CHANNEL 2 INPUT CHANNEL 10 INPUT CHANNEL 3 INPUT CHANNEL 11 INPUT CHANNEL 4 INPUT CHANNEL 12 INPUT CHANNEL 5 INPUT CHANNEL 13 INPUT CHANNEL 6 INPUT CHANNEL 14 INPUT CHANNEL 7 INPUT CHANN...

Page 74: ...3 3 3 INPUT CHANNEL 1 INPUT CHANNEL 9 INPUT CHANNEL 2 INPUT CHANNEL 10 INPUT CHANNEL 3 INPUT CHANNEL 11 INPUT CHANNEL 4 INPUT CHANNEL 12 INPUT CHANNEL 5 INPUT CHANNEL 13 INPUT CHANNEL 6 INPUT CHANNEL...

Page 75: ...OR 10 V TO 10 V EXTERNAL COMMON EXTERNAL 24 VDC 4 20 mA RL2 RL RL CHANNEL 5 SYSTEM POWERED 4 20 mA CHANNEL 8 EXTERNALLY POWERED 4 20 mA TP35266A CHANNEL 6 SINGLE ENDED VOLTAGE CHANNEL 3 3 WIRE RTD JUM...

Page 76: ...CABLE I O COM 10 V TO 10 V SINGLE ENDED VOLTAGE VSOURCE C NON ISOLATED IMASI03 NKAS02 12 CABLE DIFFERENTIAL VOLTAGE RL1 RL2 C IMASI03 NKAS02 12 CABLE 24 V EXTERNAL 24 V I O COM NON ISOLATED EXTERNAL C...

Page 77: ...CABLE I O COM 10 V TO 10 V SINGLE ENDED VOLTAGE VSOURCE C NON ISOLATED IMASI03 NKAS02 12 CABLE DIFFERENTIAL VOLTAGE RL1 RL2 C IMASI03 NKAS02 12 CABLE 24 V EXTERNAL 24 V I O COM NON ISOLATED NIAI05 TER...

Page 78: ...vision A and B Hardware NIAI05 TP35262A P1 P3 J2 J3 J1 P2 NKAS02 12 SEE NOTE ANALOG SLAVE TERMINATION CABLE NIAI05 NIAI05 CHANNELS 1 8 ON J2 CHANNELS 9 16 ON J3 IMASI03 FIELD WIRING FIELD WIRING NOTE...

Page 79: ...ature of the termination unit This temperature is used to compensate for the cold junction effect on thermo couple inputs When using the built in cold junction reference the termina tion unit covers s...

Page 80: ...d minus inputs directly to IMASI03 differential input Channel to channel and channel to system signal isolation is achieved for all voltage input types including high level voltage millivolts and ther...

Page 81: ...ision B hard ware Check jumpers before installing the NTAI06 Figure B 3 shows a typical input circuit and the jumpers used for each input Figure B 4 shows field input termination examples for revi sio...

Page 82: ...C C C C C 1 2 5 6 3 7 4 8 J1 J17 J2 J18 J19 J4 J20 J3 J33 J49 J34 J50 J35 J51 J36 J52 J37 J53 J38 J54 J39 J55 J40 J56 J5 J21 J6 J22 J7 J23 J8 J24 J9 J25 J10 J26 J11 J27 J12 J28 J41 J57 J42 J58 J43 J59...

Page 83: ...24V P2 C 13 C C C 16 15 14 C C C C 9 10 11 12 C C C C C C C C 1 2 5 6 3 7 4 8 J1 J17 J2 J18 J19 J4 J20 J3 J33 J49 J34 J50 J35 J51 J36 J52 J37 J53 J38 J54 J39 J55 J40 J56 J5 J21 J6 J22 J7 J23 J8 J24 J...

Page 84: ...2 2 2 3 3 3 3 INPUT CHANNEL 1 INPUT CHANNEL 9 INPUT CHANNEL 2 INPUT CHANNEL 10 INPUT CHANNEL 3 INPUT CHANNEL 11 INPUT CHANNEL 4 INPUT CHANNEL 12 INPUT CHANNEL 5 INPUT CHANNEL 13 INPUT CHANNEL 6 INPUT...

Page 85: ...1 J57 J42 J58 J43 J59 J44 J60 J13 J29 J14 J30 J15 J31 J16 J32 J45 J61 J46 J62 J47 J63 J48 J64 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16 GND...

Page 86: ...OM 10 V TO 10 V SINGLE ENDED VOLTAGE VSOURCE C NON ISOLATED IMASI03 NKAS01 11 CABLE DIFFERENTIAL VOLTAGE RL1 RL2 C IMASI03 NKAS01 11 CABLE 24 V EXTERNAL 24 V I O COM NON ISOLATED NTAI06 TERMINATION UN...

Page 87: ...able Connections for NTAI06 TP35256A P1 P3 J3 J2 J1 P2 NKAS01 11 SEE NOTE ANALOG SLAVE TERMINATION UNIT CABLE NTAI06 CHANNELS 11 16 CHANNELS 1 10 IMASI03 FIELD WIRING NOTE NKAS01 HAS PVC INSULATION SP...

Page 88: ...in this appendix is for reference only Refer to the Function Code Application Manual I E93 900 20 for current information on the function codes ENHANCED ANALOG SLAVE DEFINITION FUNCTION CODE FC 215 T...

Page 89: ...N 2 Represents the amount of time between successive updates of an individual channel s input value and quality Table C 3 FC 215 Specifications Spec No Tune Default Value Data Type Range Min Max Descr...

Page 90: ...nd Note 3 in Table C 7 Figure C 2 shows an example of remote cold junction reference Select the cold junction reference input by configuring specifi cation 3 of function code 215 with the block output...

Page 91: ...re parameters Figure C 2 Remote Cold Junction Compensation R 30 L1 2 TYPE S THERMOCOUPLE R 30 L2 R 20 L1 TYPE R THERMOCOUPLE R 20 L2 IMASI03 REMOTE TERMINAL BLOCK IMASI03 TO T D CABLE TERMINATION DEVI...

Page 92: ...sts the output descriptions of function code 216 Table C 6 lists the specifications of function code 216 Table C 4 FC 216 Outputs Block No Data Type Description N REAL Analog input value and quality i...

Page 93: ...nge for example 1 to 5 V any signals detected to fall five percent outside of that range will be marked as bad quality with a status indication of out of range Table C 6 FC 216 Specifications Spec No...

Page 94: ...03850 x23 120 Ohm Chemically pure Nickel RTD TCR 0 00672 x24 10 Ohm Copper RTD TCR 0 00427 x25 Chinese 53 Ohm Copper RTD x40 1 to 5 V 4 20 mA x41 10 to 10 V x42 0 to 10 V x43 0 to 5 V x60 100 to 100 m...

Page 95: ...pec ification defines the lower limit of the range in Volts S9 This specification is ignored unless the input signal type S4 indicates a user specified voltage range In that case this spec ification d...

Page 96: ...ls ENHANCED CALIBRATION COMMAND FUNCTION CODE FC 217 This function code is used to calibrate the IMASI03 Slave Input Module The operator initiates guides and terminates a calibration sequence with thi...

Page 97: ...calibration operation performed on the referenced channel The third and fourth outputs give the user specified gain and offset adjustment values for the referenced channel These will be initially 1 0...

Page 98: ...If none has been specified this value will be 1 N 3 User offset adjustment This output gives the value of the user specified offset adjustment If none has been specified this value will be 0 The unit...

Page 99: ...a point User gain and offset values will be reset to 1 0 and 0 0 respectively if a successful calibration has been performed 4 Point Escape The Point Escape command is used to reset clear calibration...

Page 100: ...these modules Intended as an additional diagnostic for the slave interface It requires an MFP 11 Restore factory calibration command This command overwrites the field calibration data in NVRAM with t...

Page 101: ...e default value for gain is set to one and the default value for off set is set to zero This command sets both the gain and offset parameters simultaneously each time it is entered Example Low level m...

Page 102: ...Connections Input 6 9 Connections Output 6 9 Connectors P1 P2 P3 3 5 Continue Do Not Display Error 6 6 Corrective Actions for Error Messages 6 2 D Data on Input Channels 6 2 Data Values 2 5 Diagnostic...

Page 103: ...n 2 7 2 9 Input Channel Data 6 2 Input Connections 6 9 Input Multiplexer MUX 2 2 Input Processing 2 6 Inputs Calibrating 4 2 Inputs Configuring the 4 1 Isolation Amplifier 2 2 J Jumper Configuration 3...

Page 104: ...us Communication Security 2 10 Open Input Detection 2 10 Select Slave Address 3 2 Setup and Installation Address Switch SW1 3 2 Binary Slave Address 3 3 Configuring Inputs 3 3 Jumper Configuration 3 4...

Page 105: ...756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefax...

Reviews: