DESCRIPTION AND OPERATION
ON-LINE CONFIGURATION
I-E96-301B
2 - 11
ON-LINE CONFIGURATION
All specifications in function codes 215, 216 and 217 associ-
ated with the IMASI03 may be changed during on-line configu-
ration. When changes are made to the input channel
parameters (function code 216), the channel will hold the last
value for a short period, the status remains unchanged during
this period. This hold time is based on the number of channels
that were changed during on-line configuration, as well as the
resolution specified in the function code 216 blocks for that
channel. Plan on a hold time of four seconds (worst case) for
each function code 216 changed during on-line configuration.
LOGIC POWER
The IMASI03 receives its power (+5 V,
±
15 V) from the MMU
backplane. Power connects through the top 12-pin card edge
connector (P1) at the back of the IMASI03.