DL205 User Manual, 4th Edition, Rev. B
5–335
Chapter 5: Intelligent Box (IBox) Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
CTRIO Clear Preset Table (CTRCLRT) (IB-1007)
CTRIO Clear Preset Table will clear the RAM based Preset Table on a leading edge transition
to this IBox. This IBox will take more than
one PLC scan to execute. Either the Success
or Error bit will turn on when the command
is complete. If the Error Bit is on, you can use
the CTRIO Read Error Code (CTRRDER)
IBox to get extended error information.
The Workspace register is for internal use by
this IBox instruction and MUST NOT be
used anywhere else in your program.
CTRCLRT Parameters
• CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config)
• Output#: specifies a CTRIO output to be used by the instruction
• Workspace: specifies a V-memory location that will be used by the instruction
• Success: specifies a bit that will turn on once the instruction has successfully completed
• Error: specifies a bit that will turn on if the instruction does not complete successfully
DS5
Used
HPP
N/A
Parameter
DL205 Range
CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
K0-255
Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
K0-3
Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
See DL205 V-memory map - Data Words
Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
See DL205 V-memory map
Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
See DL205 V-memory map
ý
ý
þ
þ
230
240
2
5
0
-1
2
6
0