Chapter 5: Standard RLL Instructions - Boolean
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
And (AND)
The And instruction logically ands a normally open
contact in series with another contact in a rung. The
status of the contact will be the same state as the
associated image register point or memory location.
And Not (ANDN)
The And Not instruction logically ands a normally
closed contact in series with another contact in a rung.
The status of the contact will be opposite the state of
the associated image register point or memory location.
In the following And example, when input X1 and X2 are on output Y5 will energize.
In the following And Not example, when input X1 is on and X2 is off output Y5 will
energize.
Aaaa
Aaaa
Operand Data Type
DL230 Range DL240 Range
DL250-1
DL260 Range
A
aaa
aaa
aaa
aaa
Inputs X
0–177
0–477
0–777
0–1777
Outputs Y
0–177
0–477
0–777
0–1777
Control Relays C
0–377
0–377
0–1777
0–3777
Stage S
0–377
0–777
0–1777
0–1777
Timer T
0–77
0–177
0–377
0–377
Counter CT
0–77
0–177
0–177
0–377
Special Relay SP
0-117, 540-577
0-137, 540-617
0-137, 540-717
0-137, 540-717
Global GX
-
-
-
0-3777
Global GY
-
-
-
0-3777
STR
$
1
B
ENT
2
C
ENT
OUT
GX
5
F
ENT
AND
V
Y5
OUT
X1
X2
Handheld Programmer Keystrokes
Direct
SOFT
ANDN
W
STR
$
1
B
ENT
2
C
ENT
OUT
GX
5
F
ENT
X1
Y5
OUT
X2
Handheld Programmer Keystrokes
Direct
SOFT
þ
þ
þ
þ
230
240
250-1
260
þ
þ
þ
þ
230
240
250-1
260
DS
Implied
HPP
Used