DL205 User Manual, 4th Edition, Rev. B
5–246
Chapter 5: Intelligent Box (IBox) Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Hi/Low Alarm - Binary (HILOALB) (IB-401)
Hi/Low Alarm - Binary monitors a binary (decimal) V-memory location and sets four
possible alarm states, High-High, High, Low, and Low-Low whenever the IBox has power
flow. You enter the alarm thresholds as constant (K) decimal values (K0-K65535) and/or
binary (decimal) V-memory locations.
You must ensure that threshold limits are valid,
that is HH >= H > L >= LL. Note that when
the High-High or Low-Low alarm condition is
true, that the High and Low alarms will also be
set, respectively. This means you may use the
same threshold limit and same alarm bit for the
High-High and the High alarms in case you
only need one "High" alarm. Also note that the
boundary conditions are inclusive. That is, if
the Low boundary is K50, and the Low-Low
boundary is K10, and if the Monitoring Value
equals 10, then the Low Alarm AND the Low-Low alarm will both be ON. If there is no
power flow to the IBox, then all alarm bits will be turned off regardless of the value of the
Monitoring Value parameter.
HILOALB Parameters
• Monitoring Value (Binary): specifies the V-memory location of the Binary value to be monitored
• High-High Limit: V-memory location or constant specifies the high-high alarm limit
• High-High Alarm: On when the high-high limit is reached
• High Limit: V-memory location or constant specifies the high alarm limit
• High Alarm: On when the high limit is reached
• Low Limit: V-memory location or constant specifies the low alarm limit
• Low Alarm: On when the low limit is reached
• Low-Low Limit: V-memory location or constant specifies the low-low alarm limit
• Low-Low Alarm: On when the low-low limit is reached
Parameter
DL205 Range
Monitoring Value (Binary) . . . . . . . . . . . . . . . . V
See DL205 V-memory map - Data Words
High-High Limit . . . . . . . . . . . . . . . . . . . . . . . V, K
K0-65535; or see DL205 V-memory map - Data Words
High-High Alarm . . . . . . . . . . . X, Y, C, GX,GY, B
See DL205 V-memory map
High Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . V, K
K0-65535; or see DL205 V-memory map - Data Words
High Alarm . . . . . . . . . . . . . . . . X, Y, C, GX,GY, B
See DL205 V-memory map
Low Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . V, K
K0-65535; or see DL205 V-memory map - Data Words
Low Alarm . . . . . . . . . . . . . . . . X, Y, C, GX,GY,B
See DL205 V-memory map
Low-Low Limit . . . . . . . . . . . . . . . . . . . . . . . V, K
K0-65535; or see DL205 V-memory map - Data Words
Low-Low Alarm. . . . . . . . . . . . . X, Y, C, GX,GY, B
See DL205 V-memory map
DS5
Used
HPP
N/A
ý
ý
þ
þ
230
240
2
5
0
-1
2
6
0