When configuring a Remote I/O channel for
fewer than 7 slaves, we must fill the
remainder of the table with zeros. This is
necessary because the CPU will try to
interpret any non-zero number as slave
information.
We continue our setup program from the
previous page by adding a segment which
fills the remainder of the table with zeros.
The example to the right fills zeros for slave
numbers 2–7, which do not exist in our
example system.
On the last rung in the example program above, we set a special relay contact C740. This
particular contact indicates to the CPU the ladder program has finished specifying a remote
I/O system. At that moment the CPU begins remote I/O communications. Be sure to include
this contact after any Remote I/O setup program.
Remote I/O Test Program
Now we can verify the remote I/O link and
setup program operation. A simple quick
check can be done with one rung of ladder,
shown to the right. It connects the first input
of the remote base with the first output.
After placing the PLC in RUN mode, we can
go to the remote base and activate its first
input. Then its first output should turn on.
DL205 User Manual, 4th Edition, Rev. B