DL205 User Manual, 4th Edition, Rev. B
5–315
Chapter 5: Intelligent Box (IBox) Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
ECWRSNM Example
Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all
ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as
ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move
the module in the base to a different slot, then you only need to change this one IBox. V400
is used as a global result status register for the other ECxxxx IBoxes using this specific
ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx
IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer
available for use by the other ECxxxx IBoxes using this specific ECOM100 module.
NOTE
: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in
BOLD italics
, and the instruction name and ID will be in
BOLD characters.
Rung 2: On the 2nd scan, assign the Subnet Mask of the ECOM100 to 255.255.0.0
The ECWRSNM is leading edge triggered, not power-flow driven (similar to a counter input
leg). The command to write the Subnet Mask will be sent to the ECOM100 whenever the
power flow into the IBox goes from OFF to ON.
If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at
V2000 for the specific error code.
To configure all of the ECOM100 TCP/IP parameters in one IBox, see the ECOM100 IP
Setup (ECIPSUP) IBox.
ECOM100
Config
ECOM100
IB-710
ECOM100#
Slot
Status
Workspace
Msg Buffer (65 WORDs)
K0
K1
V400
V401
V402-502
1