MODULEX CONTROLLER OPERATION
A-11
EXPERT MENU TABLE -
Continued
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
- Continued
HYSTERESIS
Dynamic Switching hysteresis stage 1.
(Not Applicable)
5K - 20K
(N/A)
5.0K
(N/A)
FOUND MODULS
Display of heat generators automatically
reported via BUS with BUS ID. Displays the
number of heat modules available for service.
display
CAP/MODULE
After restarting, the Controller, searches the
bus systems for available new heat modules
and the maximum kW output of each heat
module.
00 - 1000 kW
40 kW
NEW CONFIG
If the BUS configuration was modified, the
automatic search for generators on the BUS
may be activated here.
(Currently Not Applicable)
00, 01 (OFF/ON)
(N/A)
00
(N/A)
MIN MOD CASC
Specifies the number of heat modules started
simultaineously.
01 - 08
01
HW-BOILER
Number of stages for HW operation
00 - 08
00
CONTR DEVIAT
Control Deviation indicates the temperature
difference between the header set point and
the actual temperature.
display
F
DES OUPUT
Required system output [in %]
0 - 100%
00
SWITCH TIME
Internal control value: only for switching
cascade
(-99) - 0 - (99)
Display
(N/A)
BLOCK TIME
Not Applicable
(N/A)
(N/A)
MAX T-MODUL
Maximum temperature of Heat Module
50.0°C
–
110.0°C
90.0°C
DYN UPWARD
Dynamic heat generator connection
(Not Applicable)
(N/A)
(N/A)
DYN
DOWNWARD
Dynamic heat generator deactivation
(Not Applicable)
(N/A)
(N/A)
RESET TIME
Resetting time for Controller (seconds)
5 - 500
50
MODULAT MAX
Start Level. If this modulation percentage is
exceeded, the next heat generator (module) is
connected after the delay time specified by
the SEQ SW TIME (see below) elapses.
50% - 100%
30%
MODULAT MIN
Stop Level. If value drops below this
modulation percentage, the last heat
generator (module) of the current sequence is
switched off
10% - 60%
35%
MIN MOD HS
Connection of the next heat generator
0% - 60%
35%
MOD LEVEL HW
Entry of the set modulation percentage for the
heat generators in hot water operation
(Currently Not Applicable)
40% - 100%
(N/A)
80%
(N/A)
SEQUENCE 1
Boiler sequence 1
12345678
SEQUENCE 2
Boiler sequence 2
87654321