MODULEX CONTROLLER OPERATION
17
NOTE
Whenever
“CODE NO.” is displayed, it indicates that the valid password
must be entered. This is accomplished by entering code 0000 (4 zeros)
by pressing the Program Key 4 times.
Table 3-3. EXPERT Menu Listing
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
CODE-NO
Permits entry of valid Code No.(0000)
0000 - 9999
0000
BUS ID 1
The heating circuits are sequentially
numbered starting with "01", heating circuit
numbers must not be assigned twice
(00), 01 - 15
01
BUS ID 2
The heating circuits are sequentially
numbered starting with "01", heating circuit
numbers must not be assigned twice
(00), 01 - 15
- - - -
AF SUPPLY
Outdoor sensor power supply
00, 01 (OFF/ON)
01 (ON)
BUS TERM
Bus terminating resistor (Must be set to 01)
00, 01 (OFF/ON)
01 (ON)
EBUS SUPPLY
Switches the eBUS supply ON/OFF
00, 01 (OFF/ON)
01 (ON)
TIME MASTER
Not Applicable
MAX T-COLL
Sets the maximum allowable header set point
temperature.
30.0
°
- 11.0
°
C
85
°
C
MIN T-COLL
Sets the minimum allowable header set point
temperature.
10.0
°
- 80.0
°
C
10
°
C
MAX T-HS2
Not Applicable
MIN T-HS2
Not Applicable
V-CURVE
0 to 10 Volt input Voltage curves. Choose
from preset curves (see para. 3.5.1) or
customize a curve.
00 - 11
11
CURVE 11-U1
Low voltage setting
0.00V
– 10.00V
0.000
CURVE 11-U2
High voltage setting
0.00V
– 10.00V
10.00
CURVE 11-T1
Minimum set point temperature
0.00 - 120.0°C
15°C
CURVE 11-T2
Maximum set point temperature
0.00 - 120.0°C
85°C
CURVE 11-UA
Stop/Start voltage level. Going below/above
this setting will stop/start the Boiler.
0.00V
– 10.00V
1.00