MODULEX CONTROLLER OPERATION
19
Table 3-3. EXPERT Menu Listing -
Continued
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
- Continued
SEQU CHANGE
Sequence change mode
01 - 06
06
SEQ SW TIME
Time to sequence change (hours)
10 - 800
200
LOCK TIME
Not Applicable
00 min - 30 min
00
HYST BURNER2
Not Applicable
HS COOL-FCT
Not Applicable
T-HS COOL
Not Applicable
HEATSOURCE 1
Identification of Boiler Type being used:
00 = No Boiler
01 = Single-Stage, switching
02 = Single-Stage, modulating
03 = 2-Stage, switching
04 = 2 individual, switching
05 = Multi-Stage, switching
06 = Multi-Stage, modulating (cascade via
BUS)
See
DESCRIPTION
06
(Multi-Stage
Modulating)
HS 1 BUS
Communication connection between
Controller and Heat Source
00 - 04
02
HEATSOURCE 2
Not Applicable
N/A
N/A
STORAGE HS2
Not Applicable
N/A
N/A
BUFFER
Not Applicable
N/A
N/A
SCREED
Not Applicable
N/A
N/A
SCREED PROGR
Not Applicable
N/A
N/A
RETURN
Press Program Key to exit INSTALLATION
Sub-Menu.
HOT WATER Sub-Menu
DHW RELIEF
Not Applicable
N/A
N/A
PARALLEL
Parallel pump operation.
00 = Hot Water Priority
01 = Hot Water Partial Priority
02 = Pump Parallel Running
00, 01, 02
01
T-BOILER DHW
Boiler temperature increase during Hot Water
operation.
Boiler Temp = (DHW Temp Setting) + (T-
BOILER DHW)
0.0°C
– 90.0°C
20 K
HYST DHW
Hot Water Hysteresis
5.0°C
– 30.0°C
5.0°C
DHW FOLLOWUP
Pump Run-Down Time
00 min.
– 30 min.
00 min.
THERM INPUT
Storage Tank With Sensor = 00
Storage Tank With Thermostat = 01
00, 01
00
WALL HUNG
Not Applicable
LOAD THROUGH
Not Applicable
RETURN
Press Program Key to exit HOT WATER Sub-
Menu.