MODULEX CONTROLLER OPERATION
A-5
A-2.
USER AREA
The USER area contains exactly the same main areas as the DISPLAY area. However, the USER area
items are not
“Read Only” and therefore can be changed if the desired values are not displayed.
USER MENU TABLE
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
LANGUAGE
Selects display language.
12 different
languages are
available.
ENGLISH
CONTRAST
Adjusts display contrast
-20 to 20
00
DISPLAY SEL
Sets the day of the week or the sensor
temperature (°C) to appear in the display
when the swing-down panel is closed.
Day:
SUN
– SAT
T-OUTSIDE:
Outside Temperature
FLOW TEMP (1/2): Flow Temp. For Heating
Circuit 1 or 2 supply
water temperature.
(Only if sensor is
installed)
T-DHW:
Domestic Hot Water
Temp
T-BOILER;
Heat Generator Temp.
T-ROOM (1 / 2):
Room Temp, Heating
Circuit 1 or 2 (ONLY if
Remote Control is
connected)
See
DESCRIPTION
Column
- - - -
RETURN
Press Program Key to exit INSTALLATION
Sub-Menu.
HOT WATER Sub-Menu
1X DHW
Enables storage tank for heating
00, 01 (OFF/ON)
00 = OFF
T-DHW 1, 2 or 3
Hot Water set point for enable time 1, 2, or 3
10°C - 70°C
60°C
BOB-VALUE
Currently Not Applicable
(N/A)
(N/A)
CIRCL-P-DHW
Circulation Pump for Domestic Hot Water
00, 01 (OFF/ON)
00 = OFF
RETURN
Press Program Key exit HOT WATER Sub-
Menu.